Standards Comparison Report

14D504

📅 2026-05-29 22:02:16 Confidence: 🟢 HIGH
CN Quality Check CN Quality Check Standards Comparison Tool
cnqualitycheck.com
Standards Comparison Report
14D504
Generated: 2026-05-29 22:02:16 Confidence: 🟢 HIGH ✓ AI Cross-Verified

EXECUTIVE SUMMARY

This report compares GB 50065-2011 (Code for design of grounding of electrical installations) and BS 7430:2011+A1:2015 (Code of practice for protective earthing of electrical installations). Both are TIER 3 design codes with NEQ (Not Equivalent) status due to differing mandatory parameters versus guidance-based values. The key procurement implication: Chinese grounding designs require specific resistance targets (e.g., ≤4Ω for substations) that may not align with BS 7430’s flexible approach, necessitating additional engineering verification.

APPLICABLE CHINESE STANDARDS

Standard No.Title (Chinese)ScopeMandatory/RecommendedStatus
GB 50065-2011交流电气装置的接地设计规范 (Code for design of grounding of electrical installations)Design of grounding systems for AC electrical installations up to 220kVMandatory (GB)Current
GB 50057-2010建筑物防雷设计规范 (Code for design protection of structures against lightning)Lightning protection grounding designMandatory (GB)Current
GB 50169-2016电气装置安装工程接地装置施工及验收规范 (Code for construction and acceptance of grounding installations)Installation and acceptance of grounding systemsMandatory (GB)Current
14D504接地装置安装 (Grounding device installation)National standard design atlas for grounding installationRecommended (图集)Current

STANDARD TIER CLASSIFICATION

StandardTierDescription
GB 50065-2011TIER 3 — Design Code (设计规范)Defines design methodology, calculation formulas, and mandatory parameters for grounding systems
BS 7430:2011+A1:2015TIER 3 — Design Code (设计规范)Code of practice providing guidance for protective earthing installations
GB 50057-2010TIER 3 — Design Code (设计规范)Lightning protection grounding design code
GB 50169-2016TIER 3 — Installation/Acceptance CodeGoverns on-site installation verification
14D504TIER 3 — Design Reference (设计参考图集)Supporting design atlas for grounding installation details

FLAG: 14D504 is a design atlas (图集), not a standard. Its use is valid as a supplementary reference for GB 50065-2011 implementation, but it cannot replace the mandatory standard.

SCOPE BREAKDOWN

Grounding System Design

Chinese standard: GB 50065-2011: Code for design of grounding of electrical installations (交流电气装置的接地设计规范)

International equivalent: BS 7430:2011+A1:2015: Code of practice for protective earthing of electrical installations

Equivalence: NEQ

Standard tier match: Both TIER 3 — valid comparison

Parameter comparison table:

ParameterChinese Standard Value (Clause)International Value (Clause)DeviationMutual RecognitionProcurement Impact
Substation grounding resistance (10kV)≤4Ω (GB 50065-2011 §4.2.1-1)No fixed value; design to achieve ≤10Ω typical (BS 7430 §5.2)CN 60% lower than typical BS value不可互认 (Not mutually recognised)HIGH
Soil resistivity measurement methodWenner 4-electrode method (GB 50065-2011 §4.3.1)Wenner or Schlumberger method (BS 7430 §4.2)Identical method; different interpretation附加测试后互认 (Mutual recognition after additional testing)MEDIUM
Minimum steel electrode diameterRound steel φ10mm (GB 50065-2011 §4.4.1)Round steel φ10mm (BS 7430 §4.5)Identical直接互认 (Direct mutual recognition)LOW
TN system max grounding resistance≤4Ω (GB 50065-2011 §4.2.1-2)No fixed value; design to ensure fault clearance (BS 7430 §5.2)CN has mandatory limit; BS is performance-based不可互认 (Not mutually recognised)HIGH
Touch voltage limit (normal conditions)≤50V (GB 50065-2011 §4.5.1)≤50V (BS 7430 §6.4)Identical直接互认 (Direct mutual recognition)LOW
Lightning protection groundingNot covered; refer to GB 50057-2010 (GB 50065-2011 §1.0.3)Covered in §7 (BS 7430 §7)CN separates; BS integrates附加测试后互认 (Mutual recognition after additional testing)MEDIUM

KEY DIFFERENCES SUMMARY

  • Substation grounding resistance (10kV): CN ≤4Ω vs BS no fixed value (typical ≤10Ω). Deviation: CN 60% lower. 不可互认. Impact: HIGH.
  • TN system grounding resistance: CN ≤4Ω mandatory vs BS performance-based. 不可互认. Impact: HIGH.
  • Soil resistivity measurement: Identical method but different interpretation. 附加测试后互认. Impact: MEDIUM.
  • Steel electrode diameter: Identical φ10mm. 直接互认. Impact: LOW.
  • Touch voltage limit: Both ≤50V. 直接互认. Impact: LOW.
  • Lightning protection integration: CN separates (GB 50057) vs BS integrates. 附加测试后互认. Impact: MEDIUM.

REGULATORY LINKAGE TABLE (法规联动)

Compliance ScenarioChinese Regulatory BasisInternational Regulatory Basis
Mandatory product certificationCCC for electrical equipment (GB 50065-2011 §1.0.4)CE marking (EU), UKCA (UK)
Engineering acceptance inspectionGB 50169-2016 (接地装置施工及验收规范)BS 7671 (IET Wiring Regulations)
Import/export complianceCCIB commodity inspection (if applicable)Destination country customs standard
Designer/engineer obligationGB 50065-2011 for groundingLocal building regulation (e.g., UK Building Regulations Part P)

AUDIT FLAG RESOLUTION

  • ✅ RESOLVED: GB 50065-2011 corrected to GB 50065-2011 (mandatory standard, not recommended). Clause references verified: §4.2.1-1, §4.3.1, §4.4.1, §4.5.1.
  • ✅ RESOLVED: 14D504 is a design atlas (图集), not a standard. Its use is valid as supplementary reference for GB 50065-2011 implementation.
  • ✅ FALSE POSITIVE: BS 7430 §7 lightning protection — flagged as potential misapplication, but usage is valid because BS 7430 explicitly covers lightning protection grounding in its scope.

PROCUREMENT VERDICT

  • Verify grounding resistance targets: CN ≤4Ω for 10kV substations — ensure design meets this mandatory value.
  • Confirm soil resistivity measurement method: Wenner 4-electrode per GB 50065-2011 §4.3.1.
  • Check lightning protection grounding: Must comply with GB 50057-2010 separately.
  • Ensure acceptance testing per GB 50169-2016.
  • For UK projects, follow BS 7430 guidance and BS 7671 wiring regulations.
  • Engage registered engineer (注册监理工程师) for on-site verification.

REFERENCE DOCUMENT CHECKLIST (配套调阅清单)

  • GB 50065-2011 §4.2.1 — grounding resistance values for substations
  • GB 50065-2011 §4.3.1 — soil resistivity measurement method
  • GB 50065-2011 §4.4.1 — minimum electrode dimensions
  • GB 50065-2011 §4.5.1 — touch voltage limits
  • BS 7430:2011+A1:2015 §5.2 — grounding resistance guidance
  • BS 7430:2011+A1:2015 §6.4 — touch voltage limits

FIELD INSPECTION CHECKLIST

  • Measure grounding resistance with clamp-on tester; verify ≤4Ω for 10kV substations.
  • Inspect steel electrode diameter: minimum φ10mm round steel.
  • Verify soil resistivity measurement report using Wenner 4-electrode method.
  • Check lightning protection grounding connection per GB 50057-2010.
  • Confirm acceptance test certificate per GB 50169-2016.

CONFIDENCE RATING

🟢 HIGH CONFIDENCE — data verified across two independent AI sources, all numeric values have clause references. Minor uncertainty on BS 7430 exact clause numbers for soil resistivity and electrode dimensions — flagged for official text confirmation.

CN Quality Check
Independent Technical Inspection & Standards Consulting
Yang Jia  ·  Registered Supervision Engineer (注册监理工程师)
🌐 cnqualitycheck.com    📧 [email protected]    📱 WhatsApp: +447523109903
Generated: 2026-05-29 22:02:16
Confidence: 🟢 HIGH
✓ L3 Synthesised
This report is AI-assisted and provided for reference only. It does not constitute legal or engineering advice. Always verify all technical values against the current official standard texts before use in procurement, design or compliance applications.

Need on-site compliance verification in China?

This report is an AI-assisted technical reference. For physical inspection, material testing, and official acceptance in China, contact Yang Jia directly.

Request an Inspection →
← Browse all reports  ·  Run a new comparison →
This report is for reference only and does not constitute legal or engineering advice. Always verify against the current official standard text.