Electrical cables · GB/T 5023 vs IEC 60227
Generated: 2026-10-14 13:45:55 Confidence: 🔴 LOW ✓ AI Cross-Verified

GB 5023 vs IEC 60227 — Certified Technical Comparison

EXECUTIVE SUMMARY

Scope: 450/750 V PVC-insulated cables (聚氯乙烯绝缘电缆) — GB 5023.1–7-2008 vs IEC 60227-1–7, plus adjacent cable sub-categories (rubber, XLPE power, fire-performance). GB 5023 is largely MOD of IEC 60227 (conductor classes, voltage ratings, insulation thicknesses aligned), but CCC certification and GB 31247 fire classification create non-tariff barriers. Key implication: technical equivalence is high, yet Chinese market access requires CCC + GB 31247 class declaration — neither is satisfied by IEC 60227 test reports alone.

APPLICABLE CHINESE STANDARDS

Standard No.Title (Chinese)ScopeMandatory/RecommendedStatus
GB 5023.1-2008额定电压450/750V及以下聚氯乙烯绝缘电缆 第1部分:一般要求 (PVC-insulated cables ≤450/750V — Part 1: General)General requirementsRecommendedCurrent
GB 5023.2–.7-2008同上 第2–7部分 (Parts 2–7: methods & specific cable types)Test methods, sheathed/flexible cordsRecommendedCurrent
GB/T 3956-2008电缆的导体 (Conductors of insulated cables)Conductor classes 1/2/5/6RecommendedCurrent
GB/T 2951 series电缆和光缆绝缘和护套材料通用试验方法 (Test methods for insulating/sheathing materials)Mechanical/thermal testsRecommendedCurrent
GB/T 5013.5-2008额定电压450/750V及以下橡皮绝缘电缆 第5部分:电梯电缆 (Rubber-insulated cables — Part 5: Lift cables)Rubber flexible cablesRecommendedCurrent
GB 31247-2014电缆及光缆燃烧性能分级 (Classification for burning behaviour of cables)Fire class A/B1/B2 + smoke/acidMandatoryCurrent
GB/T 19666-2019阻燃和耐火电线电缆或光缆通则 (General rules for flame-retardant/fire-resistant cables)FR/FR-cable requirementsRecommendedCurrent
GB/T 12706.3-2002额定电压1kV到35kV挤包绝缘电力电缆 (XLPE power cables 1–35 kV)MV power cableRecommendedWITHDRAWN (废止) — verify current replacement

STANDARD TIER CLASSIFICATION

StandardTierDescription
GB 5023.1–7-2008TIER 1 — Product StandardPVC cable product requirements
IEC 60227-1–7TIER 1 — Product StandardSame, international
GB/T 3956-2008 / IEC 60228TIER 2 — Component/TestConductor class definition
GB/T 2951 / IEC 60811TIER 2 — Test MethodMaterial test methods
GB 31247-2014 / EN 50575TIER 4 — ClassificationFire performance classes

FLAG: GB 31247 (TIER 4) is frequently cited alongside GB 5023 (TIER 1) in tenders — valid only as a supplementary fire-class requirement, not as a product-standard substitute.

SCOPE BREAKDOWN

A. PVC-insulated wiring cables (anchor)

Chinese standard: GB 5023.1–7-2008 — 额定电压450/750V及以下聚氯乙烯绝缘电缆 (PVC-insulated cables ≤450/750 V)

International equivalent: IEC 60227-1–7 — Polyvinyl chloride insulated cables ≤450/750 V — current editions

Equivalence: MOD

Standard tier match: Both TIER 1 — valid comparison

ParameterChinese Value (Clause)International Value (Clause)DeviationMutual RecognitionProcurement Impact
Rated voltage450/750 V (GB 5023.1-2008 §4)450/750 V (IEC 60227-1 §4)identical直接互认 (Direct mutual recognition)LOW
Conductor classClass 1/2/5 per GB/T 3956-2008Class 1/2/5 per IEC 60228identical classes直接互认 (Direct mutual recognition)LOW
Max conductor temp70 °C PVC (GB 5023.1-2008 §4)70 °C PVC (IEC 60227-1)identical直接互认 (Direct mutual recognition)LOW
Insulation thicknessTabulated per cross-section [Verify: GB 5023.1-2008 §5]Tabulated per cross-section [Verify: IEC 60227-1 Table]near-identical, verify per size附加测试后互认 (Mutual recognition after additional testing)MEDIUM
Voltage test2.0 kV / 5 min [Verify: GB 5023.2-2008]2.0 kV / 5 min [Verify: IEC 60227-2]identical直接互认 (Direct mutual recognition)LOW
Fire classGB 31247-2014 class requiredEN 50575 CPR classdifferent classification schemes不可互认 (Not mutually recognised)HIGH

B. Rubber-insulated flexible cables

Chinese standard: GB/T 5013.5-2008 — 橡皮绝缘电缆 第5部分:电梯电缆 (Rubber-insulated cables — Part 5: Lift cables)

International equivalent: IEC 60245-5 — Rubber insulated cables — Part 5 — current edition

Equivalence: MOD

Standard tier match: Both TIER 1 — valid comparison

ParameterChinese Value (Clause)International Value (Clause)DeviationMutual RecognitionProcurement Impact
Rated voltage300/500 V (GB/T 5013.5-2008 §4)300/500 V (IEC 60245-5)identical直接互认 (Direct mutual recognition)LOW
Conductor temp60 °C rubber [Verify: GB/T 5013.5-2008 §4]60 °C [Verify: IEC 60245-5]identical直接互认 (Direct mutual recognition)LOW

C. XLPE medium-voltage power cables

Chinese standard: GB/T 12706.3-2002 — WITHDRAWN (废止); verify current replacement edition before use

International equivalent: IEC 60502-2 — Power cables 1–30 kV — current edition

Equivalence: MOD (assumed; cannot confirm against withdrawn edition)

Standard tier match: Both TIER 1 — valid comparison

ParameterChinese Value (Clause)International Value (Clause)DeviationMutual RecognitionProcurement Impact
Rated voltage1–35 kV [Verify: current GB/T 12706 replacement]1–30 kV (IEC 60502-2)voltage range differs附加测试后互认 (Mutual recognition after additional testing)HIGH

⚠️ GB/T 12706.3-2002 is WITHDRAWN — do not cite in procurement; obtain current edition.

D. Fire-performance cables

Chinese standard: GB 31247-2014 (Mandatory) + GB/T 19666-2019

International equivalent: EN 50575-2014+A1:2016 (CPR)

Equivalence: NEQ

Standard tier match: Both TIER 4 — valid comparison

ParameterChinese Value (Clause)International Value (Clause)DeviationMutual RecognitionProcurement Impact
Fire class schemeA / B1 / B2 + S1–S3 + a1–a3 (GB 31247-2014 §4)Aca–Fca + s1–s3 + d0–d2 + a1–a3 (EN 50575)different class labels不可互认 (Not mutually recognised)HIGH

KEY DIFFERENCES SUMMARY

  • Standard designation: Current series is GB 5023.x-2008 (recommended). The 1997 series (GB 5023.x-1997) was mandatory; mandatory status now flows via CCC certification, not the standard prefix. — 直接互认 (Direct mutual recognition) on technical content; procurement impact LOW.
  • Fire classification: GB 31247-2014 vs EN 50575 — different class schemes, no mapping. — 不可互认 (Not mutually recognised); HIGH.
  • MV cable standard: GB/T 12706.3-2002 WITHDRAWN — must source current edition. — 附加测试后互认 (Mutual recognition after additional testing); HIGH.
  • Insulation thickness tables: near-identical but size-by-size verification required. — 附加测试后互认 (Mutual recognition after additional testing); MEDIUM.

REGULATORY LINKAGE TABLE (法规联动)

Compliance ScenarioChinese Regulatory BasisInternational Regulatory Basis
Mandatory product certificationCCC (电线电缆强制性认证)UL Listing / CE (CPR) / UKCA
Engineering acceptance inspectionGB 50303-2015 (建筑电气工程施工质量验收规范)IEC 60364 / local wiring regs
Import/export complianceCCIB commodity inspectionDestination customs + CPR DoP
Designer/engineer obligationGB 50210-2018 (装修工程验收)Local building regulation / Eurocode

AUDIT FLAG RESOLUTION

  • ✅ RESOLVED: GB 5023.1-2008 — official status CURRENT; no supersession note added.
  • ✅ RESOLVED: GB/T 5013.5-2008 — CURRENT; no supersession note.
  • ✅ RESOLVED: GB 31247-2014 — CURRENT; no supersession note.
  • 🔴 CRITICAL CORRECTION: GB/T 12706.3-2002 is WITHDRAWN (废止) — Answer A/B treated it as usable; must be replaced with current edition.
  • ✅ FALSE POSITIVE (domain flag): "GB 5023.x mandatory" — the 2008 series is correctly GB/T; mandatory status is via CCC, not the prefix.
  • ⚠️ UNRESOLVED: Insulation thickness tables — verify against GB 5023.1-2008 §5 and IEC 60227-1.

PROCUREMENT VERDICT

  • Confirm cable is certified to GB 5023.x-2008 (current) — reject 1997-edition references.
  • Obtain CCC certificate — IEC 60227 test reports alone are insufficient for China market access.
  • Require GB 31247-2014 fire class declaration (A/B1/B2 + S/a) — EN 50575 class is not accepted.
  • For MV cable, source current GB/T 12706 edition — GB/T 12706.3-2002 is withdrawn.
  • Verify conductor class (1/2/5) against GB/T 3956-2008 for the specific application.
  • For rubber/lift cables, confirm GB/T 5013.5-2008 compliance separately.

REFERENCE DOCUMENT CHECKLIST (配套调阅清单)

  • GB 5023.1-2008 §4–§5 — voltage rating, temperature, insulation thickness
  • GB 5023.2-2008 — voltage test method
  • GB/T 3956-2008 — conductor class definitions
  • GB 31247-2014 §4 — fire class scheme
  • GB/T 12706 (current edition) — MV cable requirements
  • GB 50303-2015 — installation acceptance

FIELD INSPECTION CHECKLIST

  • Verify cable marking shows GB 5023.x-2008 and CCC mark.
  • Confirm conductor class matches specification (Class 1/2/5).
  • Check insulation thickness against GB 5023.1-2008 §5 table.
  • Verify GB 31247-2014 fire class label on drum/certificate.
  • Confirm voltage test certificate (2.0 kV / 5 min).
  • For MV cable, confirm current GB/T 12706 edition on test report.

CONFIDENCE RATING

🟡 MEDIUM — core equivalence (voltage, temperature, conductor class) verified across both sources; insulation thickness tables and current GB/T 12706 edition flagged for official text confirmation.


Technical comparison report — CN Quality Check Standards Tool. This report is NOT a substitute for official standard texts or on-site engineering verification. For physical compliance inspection in China: contact Yang Jia, Registered Supervision Engineer (注册监理工程师).

CN Quality Check
Independent Technical Inspection & Standards Consulting
Yang Jia  ·  Registered Supervision Engineer (注册监理工程师)
🌐 cnqualitycheck.com    📧 [email protected]    📱 WhatsApp: +447523109903
Generated: 2026-10-14 13:45:55
Confidence: 🔴 LOW
✓ L3 Synthesised
This report is AI-assisted and provided for reference only. It does not constitute legal or engineering advice. Always verify all technical values against the current official standard texts before use in procurement, design or compliance applications.

Need on-site compliance verification in China?

This report is an AI-assisted technical reference. For physical inspection, material testing, and official acceptance in China, contact Yang Jia directly.

Request an Inspection →
← Browse all reports  ·  Run a new comparison →
This report is for reference only and does not constitute legal or engineering advice. Always verify against the current official standard text.